Battery Controller does not talk to hardware. It reads sensors and publishes a setpoint; an automation you write turns that setpoint into commands for your inverter.

This page covers the three things that go wrong most often: reading the wrong sensor, getting the sign backwards, and writing setpoints faster than the inverter can follow.


Which sensor to read

Read sensor.battery_controller_battery_setpoint (in W). That is the published controller target, in every control mode.

Control mode Optimal Mode values Sensor to use
follow_schedule charging / discharging sensor.battery_controller_battery_setpoint
hybrid / hybrid_plus / zero_grid charging / discharging / zero_grid sensor.battery_controller_battery_setpoint

Do not drive your inverter from optimal_power

sensor.battery_controller_optimal_power is the optimizer's recommendation — a diagnostic value. battery_setpoint is the actual published target.

Under normal operation they match. They diverge when the commitment filter locks a charge or discharge step within the same price period, and when zero-grid overrides the schedule in the hybrid modes. In both cases battery_setpoint is the one that reflects what should actually happen.

With multiple batteries, per-battery targets are published as sensor.battery_controller_battery_setpoint_<name>, already split from the combined setpoint in proportion to each battery's headroom (charging) or stored energy (discharging).


Sign conventions

This trips up almost everyone, because the input and output conventions are opposite.

Positive means Negative means
Sensors created by the integration (Total Battery Power, Battery Setpoint, Optimal Power) discharge charge
The battery power sensor you configure as input (battery_power_sensor) charge discharge
flowchart LR
    subgraph OUT["Integration OUTPUT — Battery Setpoint, Optimal Power"]
        direction LR
        out_neg["negative<br/><b>−1000 W</b>"] --- out_zero["0"] --- out_pos["positive<br/><b>+1000 W</b>"]
        out_neg_label["CHARGE"] -.- out_neg
        out_pos_label["DISCHARGE"] -.- out_pos
    end

    subgraph INP["Your INPUT sensor — battery_power_sensor"]
        direction LR
        in_neg["negative<br/><b>−1000 W</b>"] --- in_zero["0"] --- in_pos["positive<br/><b>+1000 W</b>"]
        in_neg_label["DISCHARGE"] -.- in_neg
        in_pos_label["CHARGE"] -.- in_pos
    end

    style OUT fill:#0f766e22,stroke:#0f766e
    style INP fill:#b4530922,stroke:#b45309

The input convention matches how the integration reports charge/discharge mode. If your own battery power sensor follows the output convention instead — positive for discharge — invert its sign with a template sensor before pointing the field at it:

template:
  - sensor:
      - name: "Battery Power (inverted for Battery Controller)"
        unit_of_measurement: "W"
        device_class: power
        state_class: measurement
        state: "{{ 0 - (states('sensor.my_inverter_battery_power') | float(0)) }}"

How to check you got it right

Put the integration in manual mode and set Manual Power Setpoint to a small negative value, e.g. −500 W. The battery should charge. If it discharges, your automation has the sign backwards.


Example automation

A minimal, inverter-agnostic pattern. Replace the number.inverter_* and select.inverter_mode entities with whatever your inverter integration exposes.

automation:
  - alias: "Battery Controller - Inverter Control"
    trigger:
      - platform: state
        entity_id: sensor.battery_controller_optimal_mode
      - platform: state
        entity_id: sensor.battery_controller_battery_setpoint
    action:
      - variables:
          mode: "{{ states('sensor.battery_controller_optimal_mode') }}"
          power_w: "{{ states('sensor.battery_controller_battery_setpoint') | float }}"
      - choose:
          - conditions: "{{ power_w < -50 }}" # Charging
            sequence:
              - service: number.set_value
                target: { entity_id: number.inverter_charge_power }
                data: { value: "{{ power_w | abs }}" }
          - conditions: "{{ power_w > 50 }}" # Discharging
            sequence:
              - service: number.set_value
                target: { entity_id: number.inverter_discharge_power }
                data: { value: "{{ power_w }}" }
        default:
          - service: select.select_option
            target: { entity_id: select.inverter_mode }
            data: { option: "Auto" }
flowchart TD
    T["Setpoint or mode changes"] --> V["power_w = battery_setpoint"]
    V --> D1{"power_w &lt; −50 ?"}
    D1 -->|Yes| C["Charge<br/>write abs(power_w)<br/>to charge power"]
    D1 -->|No| D2{"power_w &gt; +50 ?"}
    D2 -->|Yes| DIS["Discharge<br/>write power_w<br/>to discharge power"]
    D2 -->|No| IDLE["Inside dead zone<br/>return inverter to Auto"]

    style C fill:#0f766e22,stroke:#0f766e
    style DIS fill:#b4530922,stroke:#b45309

The ±50 W dead zone around zero keeps the automation from flapping between charge and discharge commands on tiny setpoint changes. Match it to your Zero Grid Deadband setting.


Practical guidance

Write rate

In the zero-grid and hybrid modes the setpoint updates roughly every 5 seconds. Many inverters — particularly those behind Modbus or a cloud API — will not accept writes that fast, and some will fault or rate-limit.

Two knobs control this:

  • Zero grid response time (advanced setting, default 10 s) tells the controller how long your battery takes to respond, and limits how fast setpoints are updated.
  • Zero Grid Deadband (number entity, default 50 W) suppresses updates for grid deviations smaller than the band.

If your inverter struggles, raise the response time first.

Batteries that need an explicit mode

Some inverters ignore a power setpoint unless they are first put into a manual or forced-charge mode. If yours behaves that way, set the mode in the same choose branch that writes the power value, and return it to automatic in the default branch — as the example above does with select.inverter_mode.

Power limits

Set Max charge power and Max discharge power in the battery subentry to what the hardware can actually sustain, not the nameplate peak. If the inverter tapers near the SoC limits, also fill in the SoC-dependent derating fields — otherwise the optimizer plans trades at a rate your battery will not deliver, and the realized saving falls short of the forecast.

Grid connection cap

If your connection is limited — a small fuse, or a dynamic grid tariff with a capacity component — set Max grid power in the advanced settings. The optimizer treats it as a hard constraint rather than discovering it by tripping something.


Sharing a working configuration

There is no per-brand recipe list here, because entity names differ per inverter integration, per firmware version, and sometimes per region — a wrong recipe costs more time than no recipe.

If you have a working automation for a specific inverter, please open a discussion or pull request with:

  • inverter make, model and the HA integration used (with a link)
  • the entity IDs you write to, and their units
  • whether an explicit mode change is needed before the power setpoint is accepted
  • the Zero grid response time value that turned out to be stable
  • the sign convention the inverter itself uses

Verified contributions will be collected here.